Definition of Problem

Materials needed per operation:
  • (1) WAGO® Ethernet PFC (750-842)
  • (As Needed) WAGO® 4 Point, 24VDC Digital Input (750-402)
  • (As Needed) WAGO® 2 Point, 24VDC Analog Input (750-4xx)
  • (1) WAGO® End Module (750-600)
  • (1) WAGO® 24VDC, 10A Power Supply (787-904)
  • (Multiple) Field Sensors (i.e. proximity switches, photo-eyes, limit switches, encoders, thermocouples, strain gauges, etc.)
Materials needed per system:
  • (1) Personal Computer
  • (1) I/Gear® 5.3 or later
  • (1) WAGO® I/O-Pro 32 (759-332)

A given operation is experiencing significant efficiency lags due to unknown reasons.

Definition of Solution

At a given operation, field sensors are added to automatically detect a transition from one component of cycle time to another (i.e. work time, assembly transfer time, block time, starve time). In addition to collecting the cycle time breakdown, other attribute data specific to the process is collected to provide insight into the reason for the cycle time.

WAGO® PFC Program Overview

Two sets of retentive memory registers (current and previous) are created for each of the cycle times and all of the attribute data. One set of registers contains the current value of all of the data as it is being collected. Upon completion of the cycle, the values in the current registers and copied to the previous registers and then reset. Once the previous registers are copied into, the data ready bit is toggled to instruct I/Gear® to collect the data. This approach buffers the data for a full cycle.

I/Gear® Configuration Overview

  1. A WAGO DataLink input command, which executes every second, is created to grab the data ready bit and return it to a datapoint.
  2. A WAGO DataLink input command, which executes when the data ready datapoint value changes, is created to grab all of the cycle and attribute data and return it to a datapoints.
  3. A database DataLink output command, which executes when the one of the cycle data datapoints refreshes, is created to write all of the cycle and attribute data to the database.

More I/Gear and WAGO -->